Quick Fit Connector Steam Trap Set (Flanged)

The required components of a flanged quick-fit steam trap set.

Quick Fit Connector Steam Trap Set (Flanged)
 

Component Descriptions

Part Component Function
1 Isolation Valve to isolate the trap set from the supply steam
2 Strainer to protect the trap from detritus
3 Spiratec Sensor Chamber to monitor the trap condition
4 Thermodynamic Steam Trap to discharge condensate correctly
5 Balanced Pressure Steam Trap to discharge condensate correctly
6 Inverted Bucket Steam Trap to discharge condensate correctly
7 Sight Glass to observe the condensate condition
8 Check Valve to prevent reverse flow
9 Isolation Valve to isolate the trap set from the condensate system
Arrow Top
 

Table of Parts

Part   Component Bronze Cast iron SG iron Steel Stainless steel Product details
1, 9 Isolating Valve Globe Type   BSA1 BSA2 BSA3   Bellows Sealed Stop Valves
Ball Type       M20 M20 Ball Valves
2 Strainer Fig 3 Fig 33 Fig 37SG Fig 34 Fig 36 Strainers & Filters
3* Spiratec Sensor Chamber       ST143 ST163 Steam Trap Performance Monitoring
4 Thermodynamic Steam Trap †         UTD30L Swivel Connectors & Traps
5 Balanced Pressure Steam Trap         UBP30 Swivel Connectors & Traps
6 Inverted Bucket Steam Trap †         UIB30 Swivel Connectors & Traps
7* Sight Glass †     SG253     Sight Glasses
8 Check Valve         DCV2, 3 OR 4 Check Valves

* Items 3 and 7 are not normally installed together - both are shown to indicate position.
† If item 4, or 6 is used, item 7 should be installed at least 1 metre downstream of the trap.